Wednesday, September 10, 2014

PDA Test


A.    Procedure of Dynamic Testing
1.   The test pile shall be installed using approved installation procedures.
2.   Drill 2 8mm diameter clearance holes at the distance about 2-3 times piles section size below the top level. The hole must be in opposite side one to another.
3.   Gauges shall be attached in a secure manner as to prevent slippage under impact using bolts and nut mechanism.
4.   Apply plywood cushion to the top pile
5.   At least two hammer impacts should be applied to the top pile. First drop height should be minimal to allow the testing personnel to assess the testing equipment, the driving system and the pile stresses.
6.   Subsequent impacts can then be applied by utilizing higher drop heights
7.   Upon completion of the test, the pile can be returned to acceptable production condition.


B.    Reporting of Result
The PDA engineering report primarily covers the field results and results from CAPWAP analysis (Case Pile Wave Analysis Program).
Field reports generated are:
1.  Maximum measured force
2.  Maximum calculated tension force
3.  Transferred energy
4.  Corresponding stresses
5.  Bearing Capacity using Case Method
CAPWAP Analysis reports generated are:
1.  Pile’s estimated static capacity and it’s distribution along shaft and the toe
2.  Pile’s dynamic response (damping and stiffness).

 Figure 1.  Schematic of PDA Test



 Figure 1.  Schematic of PDA Test and Out Put